2020-12-17
The basic principle of cleaning plate heat exchangers
1, stripping effect: acidic solution can dissolve the plate heat exchanger metal surface oxides, destroy the combination with the oxide skin, so that the oxide skin attached to the surface of the metal oxide off. 2, dissolution: acidic solution is easy to react with calcium, magnesium and carbonate scale, the formation of soluble compounds to dissolve the scale. 3, loosening effect: for the mixed scale containing silicate and sulfate, as calcium, magnesium, carbonate and iron oxides dissolved in acidic solution, so the residual scale will become loose and easy to flow in acidic solution. 4、Gas rise effect: acid solution and calcium, magnesium and carbonate scale reaction, will produce a large amount of carbon dioxide. In the overflow process of carbon dioxide gas in the plate heat exchanger, it has a certain lifting force on the insoluble or slowly dissolving scale layer, so the scale will fall off from the heating surface of the heat exchanger.